Silicon rubber high temperature resistant power cable
Description
A: Product features and uses: This product is fit for ac rated voltage up to and including 0.6/1 kv fixed installation from power transmission line or portable electric connecting cable, the product has heat radiation, hardy, and corrosive gas, waterproof and other characteristics, soft cable structure, the convenient radiation, high temperature (cold) environment stable electrical performance, anti-aging performance is outstanding, long service life, Widely used in metallurgy, electric power, petrochemical, electronics, automobile manufacturing and other industries.
Two: product implementation standard Q/HHTZH001.1 flame retardant fire resistance test gb12666-90 requirements
Three: use characteristics
1. Ac rated voltage: U0/U 0.6/1kV High operating temperature: 180℃ Low ambient temperature: -60℃ for fixed installation
2. The temperature of cable installation and laying should not be lower than -25℃.
3. Allowable bending radius of cable: 10 times of cable diameter: basic model and M
model | The product name |
YGC | Silicone rubber j-edge silicone rubber sheathed power cable |
YGCR | Silicone rubber j-edge silicone rubber sheath mobile flexible power cable |
YGCP | Silicon rubber j-edge silicon rubber sheath copper braided shield power cable |
YGC22 | Silicon rubber j-edge silicon rubber sheathed steel tape armored power cable |
JGG | Silicone rubber J-edge silicone rubber sheath installation line |
JGGR | Silicone rubber J edge silicone rubber sheath for mobile installation cord |
JGGP | Silicone rubber j-edge silicone rubber sheath copper braided shield installation wire |
JHXG | Silicon rubber J-edge motor wiring |
Remark: Flame-retardant silicone rubber cable model with ZR in front, copper wire in conductor core can be tinned.
Five: code M name and meaning
Said and meaning
Table 2.
Code name | Symbol meaning |
Y | Series code (Mobile flexible cable) |
G | Silicone rubber |
C | heavy |
22 | Steel tape armoured |
P | Braided copper shield |
R | Stranded conductor |
J | Motor lead wire |
Six: main technical indicators
1. Dc resistance of finished cable conductor (Class R) (in accordance with GB3956) refer to Table 1 and Table 2 in Appendix A.
At 2.20 ℃, j-edge resistance is not less than 100M ω /KM
3. Finished cable withstands ac 50HZ3.5 kV /5min voltage test without breakdown.