Rail type temperature transmitter
Description
Guide rail type temperature transmitter is the input single or double thermal resistance, thermocouple signal into output isolation of single or double line of current or voltage signal, and improve the electrical isolation performance between input, output and power supply. Guide rail temperature transmitter can be used with unit combination instrument and DCS, PLC and other systems, in petroleum, chemical, manufacturing, electric power, metallurgy and other industries of major engineering has a wide range of applications. 1, system transmission accuracy: ±0.5%×F·S ±0.2%×F·S 2, working environment temperature: -10~55℃ 3, measurement of thermal resistance allowed lead resistance: ≤15 ω 4, cold end compensation temperature accuracy: 1℃(preheating time 30 minutes) 5, current output allowed external load impedance: 4-20 ma: 0 ~ 350 Ω; 6, voltage output internal impedance: 250 ω 7, input/output/power/communication/double circuit insulation strength: DC DC≥2000V. DC, AC≥1500V. DC 8, electromagnetic interference resistance: 9, power supply: DC: DC24V±10%V AC: AC95 ~ 265V 10, input power: 1.3 ~ 2.5W(with the model) 11, dimensions: width × height × depth: Two, the use of environmental guide rail type temperature transmitter installation position shall not have strong vibration, and from the signal end, power end and space more than IEC61000-4-4: The intensity of class III industrial field electromagnetic interference in 1995, and the use of the environment shall not have a serious corrosive effect on metal, plastic parts of harmful substances. 1, input signal type thermocouple: K, E, S, B, J, R, N, T Thermal resistance: Pt100, Cu100, Cu50, BA1, BA2 guide rail temperature transmitter users in the selection of input signal type please inform the corresponding temperature range requirements of the input signal, so that the product factory to debug. Other input and output types are specially customized; 2, single loop input z.unii can have two output, double loop input each can only correspond to one output; 3. If the input signal of double-circuit product needs to be different, please contact our company; Four, type selection spectrum
model | instructions | ||||
WD- | x | x | x | x | Rail type temperature transmitter |
The input circuit | The default is single loop | ||||
D | Double circuit (isolated from each other) | ||||
Y.i road output | 1 | 4-20mA | |||
2 | 1-5V | ||||
3 | 0-10mA | ||||
4 | 0-5V | ||||
5 | 0-10V | ||||
Second output | The default value is no second output | ||||
1 | 4-20mA | ||||
2 | 1-5V | ||||
3 | 0-10mA | ||||
4 | 0-5V | ||||
5 | 0-10V | ||||
The power supply mode | The default value is 220V ac | ||||
D | 24 v dc | ||||
The input signal | Thermal resistance: Pt100, Cu100, Cu50, BA1, BA2 Thermocouple: K, E, S, B, J, R, N, T | ||||
Temperature range | / The corresponding output range |