SBW intelligent integrated temperature transmitter

SBW intelligent integrated temperature transmitter is used for thermal resistance (RTD), thermocoupl…
Description

SBW intelligent integrated temperature transmitter is used for thermal resistance (RTD), thermocouple (TC) sensor input, and its signal into the two-line system of 4~20mA DC current signal transmission to the display, recorder, PLC, DCS, etc., to achieve accurate measurement and control of temperature. Intelligent integrated temperature transmitter can be configured by HART protocol. It is the updating product of temperature measurement and control in modern industrial field and scientific research institutes, and it is the necessary product of distribution system and digital bus system. 1. Intelligent temperature transmitter with HART protocol, used to convert a variety of input signals into 4~20mA output signals 2. Input: thermal resistance (RTD), thermocouple (TC) intelligent integrated temperature transmitter product features 1. With highlighting multi-parameter LCD display, the watch head can be rotated 2. Through HART protocol, using PDA operator or PC for configuration 3. More kinds of thermal resistance input, up to 11 kinds 4. Thermocouple input types cover a wide range 5. 7. Intelligent programmable: input: thermal resistance (RTD), thermocouple (TC), output: 4~20mA input type

model

type

Measuring range

I small measuring range

Thermal resistance (RTD)

Pt100

- 200 ℃ ~ 850 ℃

10K

The Pt500, Pt1000

Bring - 200 ℃ ~ 250 ℃

10K

Cu50, Cu100

- 50 ℃ ~ 150 ℃

10K

Ni100

60 ℃ ~ 180 ℃

10K

Ni500

Bring about 60 ℃ ~ 180 ℃

10K

Ni1000

Bring about 60 ℃ ~ 150 ℃

10K

Thermocouple (TC)

B

Ω 0 ~ 1820

500K

E

- 270 ~ 1000 ℃

50 K

J

- 210 ~ 1200 ℃

50K

K

- 270 ~ 1372 ℃

50K

N

- 270 ~ 1300 ℃

50K

R

- 50 ~ 1768 ℃

500K

S

- 50 ~ 1768 ℃

500K

T

- 270 ~ 400 ℃

50K

▲ Need special customization

Output 1. Output signal: 4~20mA? High load: Max. (V power supply -7.5V) /0.022A (current output) 3. 4. Electrical isolation: U=2000VAC 5. Circuit limit: ≤22mA 6. Response time: ≤1S 7. Saturation current: low-end 3.8mA; High-end 20.5mA alarm current: Sensor damage or sensor disconnect output is 3.6mA or 22mA (except thermocouple TC) Environmental condition 1. Operating temperature: -40~85℃ 2 storage temperature: -40~100℃ 3. Cold??? 4. Protection grade: IP65, dustproof, anti-water spray 5. Shock resistance: 4G /2~150Hz 6. Voltage: negligible Measurement accuracy of 1 meter display precision: | 0.2 ℃ or less and 0.2% to 0.08% (special) 2. The measurement accuracy depends on the measurement range. Power supply voltage: U=7.5V to 45V