ZR-DJYPVP Flame retardant computer cable

This product is suitable for ac rated voltage 300/500V or DC 1000V and below electronic computer net…
Description

This product is suitable for ac rated voltage 300/500V or DC 1000V and below electronic computer network and automatic control system signal transmission, anti-interference performance requirements of higher detection devices and instrumentation connection.


Note: we can produce (ZR) flame retardant, (IA) intrinsically safe and high temperature resistant computer cables according to customer's requirements.


Zr-djypvp polyethylene J-edge pair pair copper tape total shielding PVC sheathed soft computer cable


Zr-djypvp computer cable expression method :(1 ~ 37) ×2× (0.5 ~ 2.5㎜?) ; (1 ~ 24) ×3× (0.5 ~ 2.5㎜?)


Product Structure:


1) Number of nominal pairs (groups) : 1-37 pairs (groups);


2) Conductor: annealed soft round copper wire, nominal cross section is 0.50, 0.75, 1.0, 1.5, 2.5mm? ;


3) J edge material: high-density polyethylene;


4) Shielding: copper belt shielding;


5) Jacket: black PVC;


6) Identification and length marking: there are identification marks on the outer surface of the cable, marked at an interval of no more than 1m. The marking contents include: nominal section of the conductor, number of line pairs, cable model, manufacturer M code and year of manufacture. The length marks shall be marked on the outer surface with an interval of no more than 1m.


Working conditions: laying indoor, cable trench, pipe and other occasions requiring static shielding.


Electrical performance:


1) The j-edge resistance should not be less than 2500M ω? Km;


2) There shall be continuous circuits between the pair shielding and between the pair shielding and the general shielding;


3) The core of the cable and between the core and shielding shall be subjected to 50HZ AC 2000V voltage test for 5min without breakdown.


Features:


1) The long-term permissible operating temperature of the conductor shall not exceed 70℃, and the cable shall be prevented from high temperature DIRECT current radiation or contact during use;


2) Cable laying temperature shall not be lower than 0℃;


3) The ambient temperature shall not be lower than: -40℃ for fixed laying and -15℃ for non-fixed laying;


4) Allowable bending radius for cable laying and installation: non-armored cable should not be less than 6 times of cable diameter; Armored or shielded cable should not be less than 12 times of cable diameter; Shielding layer structure of flexible cable should not be less than 6 times of cable diameter.