Intelligent pressure transmitter

Intelligent pressure transmitters are used to measure the level, density, and pressure of a liquid, …
Description

Intelligent pressure transmitters are used to measure the level, density, and pressure of a liquid, gas, or vapor and then convert it into a 4 to 20mA DC signal output. GP intelligent pressure transmitter can also communicate with HART hand operator, through which to set and monitor. The performance specifications

(Zero reference range, under reference conditions, silicone oil filled, 316L stainless steel diaphragm)

Reference accuracy±0.075% calibration range
The stability of±0.1%URL (6 months)
Influence of ambient temperatureThe zero errorPlus or minus 0.2% URL / 56 ℃
The overall error± (0.2%URL+0.18% calibration range) /56℃
The vibration influenceIn any axial direction, the vibration effect is ±0.5%URL/g at 200Hz
The power influence< ±0.5% output range/volt
Load impactThere is no load effect unless the supply voltage is changed
Electromagnetic interference/RADIO frequency interference (EMI/RFI influence)When the field intensity reaches 30V/M from 20 to 1000MHz, the output drift is less than ±0.1% range
Impact of Installation PositionZero drift is ± 0.25kpa at most. All zero drift can be corrected and the range has no effect

Functional specification

Measuring rangeSee ordering guide
Zero and rangeIt can be adjusted by local range and zero point button, or remote adjustment by HART operator
Zero positive and negative migrationFor positive zero-point migration, the upper limit of range must be ≤+URL; For zero-point negative migration, the lower limit of the range must be ≥-URL. (Check range must be greater than or equal to z.uni small range)
The output signal4 ~ 20mA DC, the user can choose linear or square root output, digital process variables superimposed on the 4 ~ 20mA DC signal, can be used by the UPPER computer using HART protocol
Damping time constantThe damping time constant is adjustable, increasing by 0.1 seconds from z.ui to 16.0 seconds
Ambient temperature limitNo LCD head- 40 ~ 85 ℃
With LCD head- 30 ~ 60 ℃
Process temperature limitSilicone oil filling- 40 ~ 104 ℃
Inert liquid filling18 ~ 85 ℃
Storage temperature limitNo LCD head- 46 ~ 110 ℃
With LCD head- 40 ~ 70 ℃
Environmental humidity0-100% relative humidity
Overvoltage limitWhen the measurement range is 6.90 MPa, the overpressure limit is 0-13.9 MPa
When the measurement range is 20.68MPa, the overpressure limit is 0 ~ 31.02MPa
When the measurement range is 41.37MPa, the overpressure limit is 0 ~ 51.71MPa
Volume change< 0.16 cm after